Low Voltage Back
 

 

 

 

 
 
Home  >> Products >> Low Voltage >> Mini Circuit Breaker >> DZ65-63 Series Miniature Circuit Breaker
 

 

 

 

 

 

 

 

 

 
1. Application
 
DZ65-63 is applicable to a line of AC 50Hz/60Hz, 230V in single pole, 400V in double, three,four poles for protecting overload and short circuit, and rated current up to 63A. It can also beused for infrequent line conversion under the normal condition.The breaker is applicable to light-ing distribution system in industrial enterprise, commercially district, high-rise building and dwell-ing house. It conforms with the standards of IEC60898.
 
 
2. Main Technical Parameter
 
Type DZ65-63
Pole
1P 2P, 3P, 4P
Rated current (A)
1,2,3,4,6,10,16,20,25,32,40,50,63
Rated voltage(V)
230 400
Ambient temperature
-5oC ~+40oC
Type of Instantaneous release
B, C, D
Rated short circuit breaking capacity Icn(KA)
10
 
 

3. Applicable conducting wire

 
Rated current(A) Nominal cross section of wire mm2
1-6A 1
10A 1.5
16,20A 2.5
25A 4
32A 6
40,50A 10
63A 16
 
 
4. The over-current protection property
 
Ambient Temperature Initial Status Test Current Expected Result Expected Result Note
30±2oC Cold position 1.13In t≥1h Non-release -
Carried out immediately after previous test 1.45In t<1h Release -
Cold position 2.55In 1s<t<60s
(In≤32A)
Release Current smoothly rises to specified value within 5s
Cold position 2.55In 1s<t<120s
(In>32A)
Release
-5oC~+40oC Cold position 3In t≥0.1s Non-release Type B
Cold position 5In t<0.1s Release Type B
Cold position 5In t≥0.1s Non-release Type C
Cold position 10In t<0.1s Release Type C
Cold position 10In t≥0.1s Non-release Type D
Cold position 20In t<0.1s Release Type D

 

 

  Back